Ideal transformer on no load:
Ideal transformer on no load:
A transformer is ideal if it has
- · No leakage flux
- · No windings resistance
- · No iron loss in core
Ideal transformer can not possible physically. But it gives
powerful tool in the analysis of a practical transformer. Properties of ideal
and practical transformer is very close each other.
Above figure shows an ideal
transformer on no load. Secondary side is open circuited. According to ideal
transformer definition primary coil is simply a coil of pure inductance. When
we apply V1 alternating voltage in primary side it creates a small magnetizing
current Im. As we know in pure inductive circuit the current lags behind the
voltage by 90˚. Hence magnetizing current Im lags behind the applied voltage by
90˚. This current creates an alternating flux Φ which is proportional to and in
phase with it. The alternating flux links both winding so it is common for two
sides and induces e.m.f. E1 in primary and E2 in secondary side. According to
Lenz’s law V1 and E1 are equal at every instant and in opposition. Magnitude of
E1 and E2 depend upon the number of turns in primary and secondary. E1 and E2
both e.m.f.s lag behind flux Φ by 90˚. E.m.f. equation of transformer proves
that primary and secondary e.m.f.s lag behind flux Φ by 90˚.
emf equation of transformer:
Consider the above figure; V1
is alternating voltage applied to primary side with frequency f. The sinusoidal
flux Φ is produced by primary side
Φ = Φm sin ωt
Instantaneous value of emf in
primary side is
E1 = – N1 dΦ / dt = – N1 d (Φm sin ωt) / dt
= – ω N1 Φm cos ωt
= – 2π f N1 Φm cos ωt
=
2π f N1 Φm sin (ωt – 90˚) ———— (i)
This equation clears that
maximum induced e.m.f value in the primary side is
Em1 = 2π f N1 Φm
r.m.s value of primary emf is
E1 = Em1 / √2 = 2πf N1 Φm / √2 = 4.44 f N1 Φm
Similarly for E2 = 4.44 f N2
Φm
For an ideal transformer E1 =
V1 and E2 = V2
Equation (i) shows that
induced primary emf E1 lags behind the flux Φ by 90˚. Since the same flux Φ
induces secondary emf E2 so E2 also lags behind the flux Φ by 90˚.
Ideal transformer on no load
phasor diagram:
Above figure shows the phasor
diagram of ideal transformer on no load. Since the flux Φ is same for both
windings so it is taken as reference phasor. We know from equation (i) primary
e.m.f E1 and secondary e.m.f E2 lag behind the flux Φ by 90˚. E1 and V1 are
equal and 180˚ out of phase with it. E1 and E2 are in phase.
Ideal transformer on load:
Upper figure shows an ideal
transformer. It has a load ZL in secondary side. As it has a load in secondary
side the secondary coil e.m.f E2 will cause a current I2 through the load ZL.
There is no voltage drop in ideal transformer so E2 = V2
E2 = I2 ZL and V2 = I2 ZL
I2 = E2 / ZL = V2 / ZL
When the secondary is loaded
the magnitude and phase of I2 with respect to V2 is determined by the
characteristics of the load. If the load is non inductive current I2 is in
phase with V2, if the load is inductive it lags, if the load is capacitive it
leads.
The secondary current I2 set
up its own m.m.f N2I2 and it has own flux Φ2 which is opposition to the main
primary flux Φ which is due to primary current I1. The secondary ampere turns
N2I2 are known as demagnetizing amp-turns. The secondary flux weakens the
primary flux. In this way primary back emf E1 tends to be reduced. The
secondary flux will change the main flux value. However, the original value of
the main flux in the core should not change. To fulfill this condition primary
side should have an m.m.f which exactly counterbalances the secondary m.m.f
N2I2.
Primary current I1 must
follow that
N1I1 = N2I2
I1 = N2 I2 / N1 = KI2
When a transformer has load
in secondary side and I2 current flows then a primary current I1 must flow to
maintain the m.m.f balance. It can be said in another word to neutralize the
demagnetizing effect of secondary current a primary current must draw so that the
common flux Φ remain constant it is not changed.
Ideal transformer on load
phasor diagram:
Figure shows the phasor
diagram of ideal transformer on load. Here the value of K is assumed unity so
primary phasors are equal to secondary. Secondary current I2 lags behind V2 or
E2 by Φ2. It is the cause of primary current I1 = K I2 = 1.I2 which is antiphase
with it.
Thus the power factor of
primary side is equal to secondary side.
Φ1 = Φ2
or cos Φ1 = cos Φ2
Since ideal transformer has
no losses, input primary power is equal to output secondary power.
V1
I1 cos Φ1 = V2 I2 cos Φ2